Retrofitting passive cooling strategies to combat heat stress in the face of climate change: A case study of a ready-made garment factory in Dhaka, Bangladesh

应对气候变化下的热应激:孟加拉国达卡一家成衣厂被动式冷却策略改造案例研究

阅读:1

Abstract

The ready-made garment industry is critical to the Bangladesh economy. There is an urgent need to improve current working conditions and build capacity for heat mitigation as conditions worsen due to climate change. We modelled a typical, mid-sized, non-air-conditioned factory in Bangladesh and simulated how the indoor thermal environment is altered by four rooftop retrofits (1. extensive green roof, 2. rooftop shading, 3. white cool roof, 4. insulated white cool roof) on present-day and future decades under different climate scenarios. Simulations showed that all strategies reduce indoor air temperatures by around 2 °C on average and reduce the number of present-day annual work-hours during which wetbulb globe temperature exceeds the standardised limits for moderate work rates by up to 603 h - the equivalent of 75 (8 h) working days per year. By 2050 under a high-emissions scenario, indoor conditions with a rooftop intervention are comparable to present-day conditions. To reduce the growing need for carbon-intensive air-conditioning, sustainable heat mitigation strategies need to be incorporated into a wider range of solutions at the individual, building, and urban level. The results presented here have implications for factory planning and retrofit design, and may inform policies targeting worker health, well-being, and productivity.

特别声明

1、本页面内容包含部分的内容是基于公开信息的合理引用;引用内容仅为补充信息,不代表本站立场。

2、若认为本页面引用内容涉及侵权,请及时与本站联系,我们将第一时间处理。

3、其他媒体/个人如需使用本页面原创内容,需注明“来源:[生知库]”并获得授权;使用引用内容的,需自行联系原作者获得许可。

4、投稿及合作请联系:info@biocloudy.com。