The control by ventilation of airborne bacterial transfer between hospital patients, and its assessment by means of a particle tracer. 3. Studies with an airborne-particle tracer in an isolation ward for burned patients

通过通风控制医院患者间空气传播细菌的扩散,并利用颗粒示踪剂进行评估。3. 在烧伤患者隔离病房中开展空气颗粒示踪剂研究

阅读:1

Abstract

Airborne-particle transfer has been studied in a burns unit using potassium iodide particles. The observed rates of transfer were in good agreement with the values predicted by a theoretical model.An estimate of the average transfer between rooms under conditions of normal activity and with correctly functioning ventilation showed that the isolation system was highly efficient, the proportion transferred being probably less than 1 in 10(5). However, the ventilation often did not function as designed and under these conditions the efficiency was reduced by a maximum of a factor of ten. These rates of transfer do not seem great enough to account for the high rate of cross-infection found in this unit.