Enhancing low voltage ride through capability of grid connected DFIG based WECS using WCA-PSO tuned STATCOM controller

利用WCA-PSO调谐的STATCOM控制器增强并网DFIG风力发电系统的低电压穿越能力

阅读:3

Abstract

This paper investigates the utilization of a STATCOM to enhance the LVRT capability of a 9 MW DFIG based Wind Power Plant (WPP) during grid faults. The STATCOM under investigation is tuned using the Water Cycle Algorithm (WCA), Particle Swarm Optimization (PSO) and a hybrid algorithm of both WCA and PSO. Simulations are carried out in MATLAB programming software, using SimScape toolbox. Performance analysis is done by investigating the ability of the test system to ride through voltage sags on the grid side, with incorporation of the STATCOM tuned using WCA, PSO and further with the hybrid WCA-PSO algorithm. To confirm effectiveness of the proposed algorithm, simulation results for the three scenarios are compared. Results show that LVRT capability of the Danish power system was met for L-G faults. However, without a STATCOM, the WPP could not ride through LLL-G faults. When STATCOM was incorporated, LVRT capability requirements were met. Voltage fluctuations reduce from 17% to 3%, without STATCOM and with WCA-PSO tuned model, respectively, during L-G faults. During LLL-G faults, voltage magnitude fluctuates from 60% to 25%, without STATCOM and with WCA-PSO tuned model respectively. WCA-PSO tuned STATCOM also resulted in the least voltage, active and reactive power overshoots.

特别声明

1、本页面内容包含部分的内容是基于公开信息的合理引用;引用内容仅为补充信息,不代表本站立场。

2、若认为本页面引用内容涉及侵权,请及时与本站联系,我们将第一时间处理。

3、其他媒体/个人如需使用本页面原创内容,需注明“来源:[生知库]”并获得授权;使用引用内容的,需自行联系原作者获得许可。

4、投稿及合作请联系:info@biocloudy.com。