An assessment of outpatient clinic room ventilation systems and possible relationship to disease transmission

对门诊诊室通风系统及其与疾病传播可能关系的评估

阅读:1

Abstract

BACKGROUND: With healthcare shifting to the outpatient setting, this study examined whether outpatient clinics operating in business occupancy settings were conducting procedures in rooms with ventilation rates above, at, or below thresholds defined in the American National Standards Institute/American Society of Heating, Refrigerating and Air-Conditioning Engineers/American Society for Health Care Engineering Standard 170 for Ventilation in Health Care Facilities and whether lower ventilation rates and building characteristics increase the risk of disease transmission. METHODS: Ventilation rates were measured in 105 outpatient clinic rooms categorized by services rendered. Building characteristics were evaluated as determinants of ventilation rates, and risk of disease transmission was estimated using the Gammaitoni-Nucci model. RESULTS: When compared to Standard 170, 10% of clinic rooms assessed did not meet the minimum requirement for general exam rooms, 39% did not meet the requirement for treatment rooms, 83% did not meet the requirement for aerosol-generating procedures, and 88% did not meet the requirement for procedure rooms or minor surgical procedures. CONCLUSIONS: Lower than standard air changes per hour were observed and could lead to an increased risk of spread of diseases when conducting advanced procedures and evaluating persons of interest for emerging infectious diseases. These findings are pertinent during the SARS-CoV-2 pandemic, as working guidelines are established for the healthcare community.

特别声明

1、本页面内容包含部分的内容是基于公开信息的合理引用;引用内容仅为补充信息,不代表本站立场。

2、若认为本页面引用内容涉及侵权,请及时与本站联系,我们将第一时间处理。

3、其他媒体/个人如需使用本页面原创内容,需注明“来源:[生知库]”并获得授权;使用引用内容的,需自行联系原作者获得许可。

4、投稿及合作请联系:info@biocloudy.com。