Chemical and biological investigations of a transformer accident at Binghamton, NY

对纽约州宾厄姆顿变压器事故的化学和生物学调查

阅读:1

Abstract

A transformer fire occurred in a state office building in Binghamton, NY on February 5, 1981. Particulates from inside surfaces of ceiling panels on 16 of the 17 floors had concentrations of polychlorinated dibenzofurans (PCDFs) ranging from less than 1 part per million (ppm) to 1200 ppm while polychlorinated biphenyl (PCB) concentrations varied from 28 ppm to 23,000 ppm. In spite of the wide variations in contaminant concentrations, complete analytical data from 11 floors showed that there was a consistent PCDF/PCB ratio (0.067 +/- 0.026) and also consistent PCDF isomer group distributions (tetra-CDFs, 33 +/- 5%; penta-CDFs, 40 +/- 3%; hexa-CDFs, 18 +/- 7%; hepta-CDFs, 6 +/- 3%). It was found that the particulate samples could be successfully ranked in order of their degree of chemical contamination by an in vitro bioassay. The bioassay was based on induction of keratinization or changes in morphology in mouse epithelial cells. Animal toxicology experiments were carried out with a soot sample containing a PCDF concentration which approximated the mean value found on the ceiling particulates. The single dose oral LD values of the soot and its benzene extract equivalent, each administered to female guinea pigs in 0.75% methyl cellulose, were 410 and 327 mg/kg, respectively. These results demonstrated that the soot matrix had virtually no effect on the toxicity of the chemical contaminants in the soot. Morphological alterations in liver tissues from animals receiving the soot were found after examination by electron and light microscopy.(ABSTRACT TRUNCATED AT 250 WORDS)

特别声明

1、本页面内容包含部分的内容是基于公开信息的合理引用;引用内容仅为补充信息,不代表本站立场。

2、若认为本页面引用内容涉及侵权,请及时与本站联系,我们将第一时间处理。

3、其他媒体/个人如需使用本页面原创内容,需注明“来源:[生知库]”并获得授权;使用引用内容的,需自行联系原作者获得许可。

4、投稿及合作请联系:info@biocloudy.com。