Legionella pneumophila in a hospital water system following a nosocomial outbreak: prevalence, monoclonal antibody subgrouping and effect of control measures

医院供水系统中嗜肺军团菌在院内感染暴发后的流行情况、单克隆抗体亚组分析及控制措施的效果

阅读:1

Abstract

Swabs and water samples from a hospital water system were cultured for legionellae over an extended period. Legionella pneumophila serogroup 1, including outbreak associated strains, were isolated in small numbers from approximately 5% of these samples despite implementation of the current DHSS/Welsh Office regulations. No cases of nosocomial legionnaires' disease were proven during the study. Physical cleaning and chemical sterilization of taps, and replacement of washers with 'approved' brands did not eradicate the organisms. Eradication of legionellae in hospital water supplies appears to be unnecessary in preventing nosocomial legionnaires' disease provided the current DHSS/Welsh Office recommendations are implemented.