Numerical Study on Transient State of Inductive Fault Current Limiter Based on Field-Circuit Coupling Method

基于场耦合法的感应故障电流限制器瞬态特性数值研究

阅读:1

Abstract

As the capacity of the power grid continues to expand, high-level fault currents might be caused during a contingency, and the problem of short-circuit current over-limitation is imminent. The high-temperature superconducting (HTS) fault current limiter (FCL) is an effective method to solve this problem. In this paper, a transient numerical model for the process of limiting current in the inductive FCL is proposed. The model is based on the coupling of multiphysics finite element simulation and a circuit model. The voltage source is used as input, which can simulate the macroscopic characteristics in the process of limiting current, such as the voltage and current waveforms, and can also simulate microscopic characteristics, such as temperature, magnetic field, and electrodynamic force distribution. The short-circuit experimental data of an air core inductive superconducting fault current limiter (SFCL) prototype was compared with the simulation results to verify the reliability of the simulation.