Experimental study and performance analysis of solar-driven exhaust air thermoelectric heat pump recovery system

太阳能驱动废气热电热泵回收系统的实验研究与性能分析

阅读:1

Abstract

Exhaust air heat recovery is of great significance for building energy conservation. Since passive heat recovery systems use temperature or enthalpy difference between outdoor air and indoor air to drive the system, the temperature of fresh air supply cannot meet indoor requirements and the exhaust heat is not fully recovered. In this study, a solar-driven exhaust air thermoelectric heat pump recovery (SDEATHP) system is tested and evaluated for its ability to recover thermal energy from exhaust air to cool or heat fresh air. An experimental platform was established to test its performance. Results show that the SDEATHP system can obtain higher fresh air supply temperature in winter and lower fresh air supply temperature in summer. The system requires only 3.12 W of power for the fans, and the average relative cooling coefficient in summer and the average relative heating coefficient can reach 50.6 and 57.9, respectively. The optimal operating current and voltage of TE modules and photovoltaic system is analyzed, and then the number and types of electrical connections for the TE modules in SDEATHP system are discussed. The SDEATHP system provides a new method for building energy recovery and fresh air supply.

特别声明

1、本页面内容包含部分的内容是基于公开信息的合理引用;引用内容仅为补充信息,不代表本站立场。

2、若认为本页面引用内容涉及侵权,请及时与本站联系,我们将第一时间处理。

3、其他媒体/个人如需使用本页面原创内容,需注明“来源:[生知库]”并获得授权;使用引用内容的,需自行联系原作者获得许可。