Effectiveness of 1-bromo-3-chloro-5,5-dimethylhydantoin against Legionella pneumophila in a cooling tower

1-溴-3-氯-5,5-二甲基乙内酰脲对冷却塔中嗜肺军团菌的有效性

阅读:1

Abstract

Cooling towers are considered to be man-made amplifiers of Legionella spp. Thus, the proper maintenance and choice of biocides is important. The only biocidal measure that has thus far been shown to be effective in field tests is the judicious use of chlorination. Perturbation studies with 1-bromo-3-chloro-5, 5-dimethylhydantoin (Bromicide; Great Lakes Chemical Corp., West Lafayette, Ind.) (BCD) were conducted on an industrial cooling tower shown to contain Legionella pneumophila. At the concentrations recommended by the manufacturer, neither the density nor the activity of L. pneumophila was affected. At comcentrations greater than 2.0 ppm (2.0 micorgram/ml) free of residual, BCD was not effective in reducing L. pneumophila to source water concentrations, nor was it effective in reducing the 2-p-iodophenyl-3-p-nitrophenyl-5-phenyl tetrazolium chloride activity of the bacterium in situ. The data indicate that at concentrations up to 2.0 ppm, BCD is not effective in these tower studies.

特别声明

1、本页面内容包含部分的内容是基于公开信息的合理引用;引用内容仅为补充信息,不代表本站立场。

2、若认为本页面引用内容涉及侵权,请及时与本站联系,我们将第一时间处理。

3、其他媒体/个人如需使用本页面原创内容,需注明“来源:[生知库]”并获得授权;使用引用内容的,需自行联系原作者获得许可。

4、投稿及合作请联系:info@biocloudy.com。