Influence of an Axial-Electromagnetic Field Treatment Device with a Solenoid Structure on Crystallization Fouling on the Tube Side of a Shell-and-Tube Heat Exchanger

轴向电磁场处理装置(螺线管结构)对壳管式换热器管侧结晶结垢的影响

阅读:1

Abstract

In this study, the influence of an axial-electromagnetic field treatment device (AEFTD) with a solenoid structure using different electromagnetic frequencies on calcium carbonate (CaCO(3)) crystallization fouling on the tube side of a shell-and-tube heat exchanger was investigated. The experimental results indicated that the application of the AEFTD could effectively reduce fouling resistance and decelerate the growth rate of CaCO(3) fouling. The opposite trend between fouling resistance and the outlet temperature of an experimental fluid indicated that the application of the AEFTD could enhance heat transfer. Meanwhile, the crystal morphologies of the fouling samples were analyzed by means of scanning electron microscopy (SEM). The axial-electromagnetic field favored the formation of vaterite as opposed to calcite. Non-adhesive vaterite did not easily aggregate into clusters and was suspended in bulk to form muddy fouling that could be carried away by turbulent flow. Furthermore, the anti-fouling mechanism of the axial-electromagnetic field is discussed in detail. The anti-fouling effect of the AEFTD on CaCO(3) fouling exhibited extreme characteristics in this study. Therefore, the effectiveness of the AEFTD is contingent upon the selection of the electromagnetic parameters.

特别声明

1、本页面内容包含部分的内容是基于公开信息的合理引用;引用内容仅为补充信息,不代表本站立场。

2、若认为本页面引用内容涉及侵权,请及时与本站联系,我们将第一时间处理。

3、其他媒体/个人如需使用本页面原创内容,需注明“来源:[生知库]”并获得授权;使用引用内容的,需自行联系原作者获得许可。

4、投稿及合作请联系:info@biocloudy.com。