Legionella contamination of a cold-water supplying system in a German university hospital - assessment of the superheat and flush method for disinfection

德国某大学医院冷水供应系统军团菌污染——过热冲洗消毒法的评估

阅读:1

Abstract

INTRODUCTION: In case of a contamination of water-supplying systems in hospitals with legionella, usually chemical disinfection measures are used for remediation. Unfortunately, it is reported, that these methods may not be sustainable, have an impact on water quality, and can even fail. As an alternative, the superheat and flush method does not need any special equipment, can be initiated in a short lead of time and does not affect the water quality. However, evidence on this disinfection measurement against legionella is lacking. We therefore investigated and report on the effectiveness and long-term results of the superheat and flush disinfection method. METHODS: During routine periodical examinations, a rising count of legionella was detected in the cold-water supplying system at a German university hospital. Adapted to an analysis of risks, effort and benefit, the superheat and flush procedure was applied twice within 6 months. RESULTS: While 33 out of 70 samples had a higher legionella count than the legal threshold of 100 CFU/100 mL (CFU - Colony Forming Units) before the first disinfection was carried out, this number could be reduced to 1 out of 202 samples after the first intervention. Additionally, in contrast to previously published studies, the effect was long-lasting, as no relevant limit exceedance occurred during the following observation period of more than two years. CONCLUSION: The superheat and flush disinfection can provide an economic and highly effective measure in case of legionella contamination and should be shortlisted for an eradication attempt of affected water-supplying systems in hospitals.

特别声明

1、本页面内容包含部分的内容是基于公开信息的合理引用;引用内容仅为补充信息,不代表本站立场。

2、若认为本页面引用内容涉及侵权,请及时与本站联系,我们将第一时间处理。

3、其他媒体/个人如需使用本页面原创内容,需注明“来源:[生知库]”并获得授权;使用引用内容的,需自行联系原作者获得许可。

4、投稿及合作请联系:info@biocloudy.com。