Seasonal mapping of NICU temperature

新生儿重症监护室温度的季节性变化图

阅读:1

Abstract

PURPOSE: To create a thermal map of ambient air, radiant, and evaporative temperatures and humidity throughout the NICU nursery by season across a calendar year. SUBJECTS: Each cubicle of the 32-bed NICU, distributed across 5 rooms, in a level III nursery was measured. METHODS: Temperatures were recorded at a consistent time on one day during January, April, July, and October. MAIN OUTCOME MEASURES: An electronic monitor (QUESTemp degrees 34; Quest Technologies, Oconomowoc, Wisconsin) was used to measure dry bulb, wet bulb, and globe thermometer temperatures. RESULTS: Analysis of variance revealed statistically significant (P < .000) differences in season, room, and season by room interaction. Room ambient air temperatures differed by less than 2 degrees F across season. Radiant temperature paralleled air temperature. Humidity, the predominant difference across season, produced evaporative temperatures considerably lower than room air temperature, and the gradient between mean nursery dry bulb temperature and wet bulb temperature was 9.3 degrees F in summer and 16.8 degrees F in winter. CONCLUSIONS: The thermal map revealed seasonal thermal differences, particularly in humidity level and evaporative temperature. Room temperature alone does not reflect the total thermal environment. Recommendations include periodic assessment of nurseries along with air, evaporative, and radiant temperatures as well as humidity to fully appreciate the impact of the thermal environment on infants.

特别声明

1、本页面内容包含部分的内容是基于公开信息的合理引用;引用内容仅为补充信息,不代表本站立场。

2、若认为本页面引用内容涉及侵权,请及时与本站联系,我们将第一时间处理。

3、其他媒体/个人如需使用本页面原创内容,需注明“来源:[生知库]”并获得授权;使用引用内容的,需自行联系原作者获得许可。

4、投稿及合作请联系:info@biocloudy.com。