The Influence of Surgical Staff Behavior on Air Quality in a Conventionally Ventilated Operating Theatre during a Simulated Arthroplasty: A Case Study at the University Hospital of Parma

手术人员行为对模拟关节置换术期间常规通风手术室空气质量的影响:帕尔马大学医院案例研究

阅读:1

Abstract

Surgical staff behavior in operating theatres is one of the factors associated with indoor air quality and surgical site infection risk. The aim of this study was to apply an approach including microbiological, particle, and microclimate parameters during two simulated surgical hip arthroplasties to evaluate the influence of staff behavior on indoor air quality. During the first hip arthroplasty, the surgical team behaved correctly, but in the second operation, behavioral recommendations were not respected. Microbiological contamination was evaluated by active and passive methods. The air velocity, humidity, temperature, and CO(2) concentration were also monitored. The highest levels of microbial and particle contamination, as well as the highest variation in the microclimate parameter, were recorded during the surgical operation where the surgical team behaved "incorrectly". Turbulent air flow ventilation systems appeared more efficient than in the past and very low air microbial contamination was reached when behavior was correct. Therefore, adherence to behavioral recommendations in operating theatres is essential to not undermine the effectiveness of the heating, ventilation, and air conditioning systems and employed resources.

特别声明

1、本页面内容包含部分的内容是基于公开信息的合理引用;引用内容仅为补充信息,不代表本站立场。

2、若认为本页面引用内容涉及侵权,请及时与本站联系,我们将第一时间处理。

3、其他媒体/个人如需使用本页面原创内容,需注明“来源:[生知库]”并获得授权;使用引用内容的,需自行联系原作者获得许可。

4、投稿及合作请联系:info@biocloudy.com。