Abstract
Accurate electric field measurement in high-voltage direct current (HVDC) environments is essential for power system monitoring. This study systematically investigates the output characteristics of a micro-electro-mechanical system (MEMS) electric field sensor under DC ionized field conditions. Using a controlled experimental platform capable of generating independent nominal electric fields and ion flows, the influence of ion current density on sensor sensitivity and offset was quantitatively analyzed. Experimental results reveal that ion flow leads to a progressive output drift and significant measurement deviations when using conventional electrostatic calibration. To address this issue, a joint calibration method incorporating ion current density is proposed. Validation experiments demonstrate that the proposed method significantly improves measurement accuracy, reducing the maximum relative error from 29.28% to approximately 5.07%. This work provides a reliable experimental basis and calibration methodology for utilizing MEMS electric field sensors in complex ionized DC environments.