Abstract
High voltage circuit breakers are one of the core equipment in power system operation, and the voiceprint signals generated during operation contain extremely rich information. This paper proposes a fault identification method for high voltage circuit breakers based on voiceprint information data. Firstly, based on the developed voiceprint information data acquisition device, the voiceprint information of a certain high voltage circuit breaker is obtained; Secondly, an improved S-transform is proposed in the article, which generates an amplitude matrix based on the S-transform of voiceprint information; Then, through the matrix Singular value decomposition method, the fault feature quantity of voiceprint information is extracted from the time-frequency angle, and the diagnosis system of the support vector machine model is established, and the system is trained to realize the fault identification of the high-voltage circuit breaker; Finally, through experimental simulation calculations, it was shown that the accuracy of the proposed fault identification method in different operating conditions reached 92.6%, verifying the good accuracy and robustness of the proposed method and equipment.