Water samples from air conditioning cooling towers receiving different treatment protocols on five large municipal buildings in San Juan, P.R., were assayed for various Legionella spp. and serogroups by using direct immunofluorescence. Several water quality parameters were also measured for each sample. Guinea pigs were inoculated with water samples to confirm pathogenicity and recover viable organisms. Legionella pneumophila serogroups 1 to 6, L. bozemanii, L. micdadei, L. dumoffii, and L. gormanii were observed in at least one of the cooling towers. L. pneumophila was the most abundant species; its density reached 10(5) cells per ml, which is within the range that is considered potentially pathogenic to humans. A significantly higher density of L. pneumophila was observed in the cooling tower water that was not being treated with biocides. Percent respiration (INT) and total cell activity (acridine orange direct count) were inversely correlated with bacterial density. This study demonstrates that Legionella spp. are present in tropical air-conditioning cooling systems and that, without continuous biocide treatment, they may reach densities that present a health risk.