Eectrical grid linked to PV/wind system based fuzzy controller and PID controller tuned by PSO for improving LVRT

基于模糊控制器和PID控制器的光伏/风力发电系统并网系统,采用粒子群优化算法(PSO)进行参数整定,以改善低电压穿越性能。

阅读:1

Abstract

This paper presents the use of a static synchronous compensators (STATCOM) device to improve the low voltage ride through (LVRT) ability of an electrical network consisting of wind farms that produce 9 MW and 1 MW PV stations during grid faults. A hybrid energy model is connected with 100 MVAR STATCOM at the point of common coupling (PCC) through line to line fault occurs on the grid. STATCOM control is used to detect the voltage at the PCC bus through occurring line to line (LL) faults by compensating reactive energy. A method of particle swarm optimization (PSO) is utilized for adjusting the optimum value of proportional-integral-derivative (PID) STATCOM control. STATCOM is controlled by (PID) and is compared with STATCOM controlled by fuzzy logic control (FLC). The proposed system has been performed utilizing Matlab/Simulink. Results of the simulation clear effectiveness and the ability of STATCOM with FLC in improving LVRT, power quality, and mitigation voltage dip, during grid faults like line to line (LL) faults as compared with STATCOM with PID control.

特别声明

1、本页面内容包含部分的内容是基于公开信息的合理引用;引用内容仅为补充信息,不代表本站立场。

2、若认为本页面引用内容涉及侵权,请及时与本站联系,我们将第一时间处理。

3、其他媒体/个人如需使用本页面原创内容,需注明“来源:[生知库]”并获得授权;使用引用内容的,需自行联系原作者获得许可。

4、投稿及合作请联系:info@biocloudy.com。