A two-stage subsynchronous oscillation assessment method for DFIG-based wind farm grid-connected system

一种基于双馈感应发电机的风电场并网系统的两阶段次同步振荡评估方法

阅读:1

Abstract

In the power system, the wind farm based on Doubly-Fed Induction Generator (DFIG) may lead to Subsynchronous Oscillation (SSO), which poses a challenge to the stability of the power grid. In order to accurately evaluate SSO, this paper proposes a new evaluation method. It is divided into two main stages: firstly, the interference level of Phasor Measurement Unit (PMU) data is identified by using the classification model based on Upper Confidence Bound (UCB) and Double Deep Q Network (DDQN). Then, an SSO parameter estimation model based on Local Feature Fusion Transformer (LFF-Transformer) network is designed for data with different interference levels. Experimental results show that the errors of eRMSE-f and EMAPE-F are 0.001 and 0.003 respectively, and the errors of eRMSE-δ and EMAPE-δ are 0.009 and 0.015 respectively. In terms of training and testing time, this method is 90 s and 18 s respectively, which is significantly better than Multi-SVR and Multi-CNN. After application, the frequency deviation decreased from 0.05 to 0.02 Hz, the voltage deviation decreased from 3.5 to 1.5%, the power fluctuation decreased from 10 to 5 MW, the SSO frequency decreased from 1.5 Hz to less than 0.5 Hz, and the SSO damping ratio increased from 0.08 to 0.15. This shows that the proposed method effectively increases the stability of the power grid.

特别声明

1、本页面内容包含部分的内容是基于公开信息的合理引用;引用内容仅为补充信息,不代表本站立场。

2、若认为本页面引用内容涉及侵权,请及时与本站联系,我们将第一时间处理。

3、其他媒体/个人如需使用本页面原创内容,需注明“来源:[生知库]”并获得授权;使用引用内容的,需自行联系原作者获得许可。

4、投稿及合作请联系:info@biocloudy.com。