Evaluating ATP testing for distribution system monitoring: comparison to HPC, impact of chlorine quenching, and hold time dependency

评估ATP检测在配电系统监测中的应用:与HPC的比较、氯猝灭的影响以及保持时间依赖性

阅读:1

Abstract

Adenosine triphosphate (ATP) assays have a faster turnaround time and higher sensitivity than traditional cultivation methods for microbial monitoring. Challenges implementing ATP testing include incompatibility with chlorine quenching agents and hold time sensitivity, which are not well-studied. Chlorinated distribution system samples were collected from two Canadian utilities, Metro Vancouver (n = 40 samples) and Halifax Water (n = 283). No significant correlations were observed between heterotrophic cell count (HPC) and cellular ATP, suggesting these do not correlate well in waters with low biological activity (median HPC < 2 CFU/mL). However, interpretation of HPC and cATP results (based on the HPC guideline of 100 CFU/mL and cATP of 10 pg/mL) yielded the same conclusion for 95% of samples, suggesting a potential decision-making framework to replace HPC with cATP. Moreover, cATP correlates better with free chlorine (p < 0.04) compared with HPC for one of the studied systems. Importantly, adding chlorine quench (10% sodium thiosulfate) did not produce significantly different cATP results, nor did analyzing at various hold times of 4-, 6-, and 24-h. This study supports the integration of ATP testing into existing sampling procedures for water utilities, as a sensitive, fast, and reliable monitoring method.