Study on the algorithm of fault recording analysis combining its time-domain waveforms with phase-domain trajectories

结合时域波形和相域轨迹的故障记录分析算法研究

阅读:1

Abstract

The untimely handling of faults in a power system has a negative impact on its operation and even the national economy, and this requires coordination in the functions of protective relaying as well as supervisory & control devices, where digital fault recorders are used to record fault waveforms of electrical physical quantities. The fault recording of a simulated current is taken as the research object in this article, and it is transformed from the time-domain waveform into a phase-domain trajectory, which is used to analyze fault feature parameters and then reformulate the waveform. The original waveform of the current will be substituted by the reformulated one with fault features to realize functions in the power system. The algorithm of reformulating fault recording, the correlativity of the reformulated waveform and its original one, and errors produced in the research process are researched. The high correlation coefficient between the reformulated waveform and its original one shows that the algorithm studied in the article offers a simple and convenient option for fault recording analysis.

特别声明

1、本页面内容包含部分的内容是基于公开信息的合理引用;引用内容仅为补充信息,不代表本站立场。

2、若认为本页面引用内容涉及侵权,请及时与本站联系,我们将第一时间处理。

3、其他媒体/个人如需使用本页面原创内容,需注明“来源:[生知库]”并获得授权;使用引用内容的,需自行联系原作者获得许可。

4、投稿及合作请联系:info@biocloudy.com。