Active frequency support capability evaluation of photovoltaic stations based on bi-level evaluation method

基于双层评价法的光伏电站有源频率支撑能力评价

阅读:1

Abstract

With the increasing penetration of photovoltaic (PV) in power grid, to cope with the deteriorating frequency security of the system, PV stations are required to participate in frequency regulation by grid codes. Knowing the active frequency support capability (AFSC) of PV stations is essential for strategy design of frequency response. Therefore, a comprehensive indicator system and an integrated evaluation method are proposed to evaluate the AFSC of PV stations. By considering several national standards, a comprehensive evaluation indicator system of AFSC for PV stations is established from three aspects: frequency stability, power support, and power regulation. In order to avoid the impact of subjective factors, this paper proposes a bi-level evaluation model combining decision-making trial and evaluation laboratory (DEMATEL), technique for order preference by similarity to ideal solution (TOPSIS), and antagonistic interpretive structural modeling (AISM) for weighting the indicators. Finally, case study was performed based on IEEE 39-bus test system integrated with PV station. The results show that the proposed indicator system and evaluation method can reflect the AFSC of PV stations effectively. The evaluation indicator system for the AFSC of PV stations is also developed into software to promote its application and implementation.

特别声明

1、本页面内容包含部分的内容是基于公开信息的合理引用;引用内容仅为补充信息,不代表本站立场。

2、若认为本页面引用内容涉及侵权,请及时与本站联系,我们将第一时间处理。

3、其他媒体/个人如需使用本页面原创内容,需注明“来源:[生知库]”并获得授权;使用引用内容的,需自行联系原作者获得许可。