Impact of air-handling system exhaust failure on dissemination pattern of simulant pathogen particles in a clinical biocontainment unit

空气处理系统排气故障对临床生物防护单元中模拟病原体颗粒传播模式的影响

阅读:7
作者:Jennifer Therkorn, David Drewry Iii, Thomas Pilholski, Kathryn Shaw-Saliba, Gregory Bova, Lisa L Maragakis, Brian Garibaldi, Lauren Sauer

Abstract

Biocontainment units (BCUs) are facilities used to care for patients with highly infectious diseases. However, there is limited guidance on BCU protocols and design. This study presents the first investigation of how HVAC (heating, ventilation, air-conditioning) operating conditions influence the dissemination of fluorescent tracer particles released in a BCU. Test conditions included normal HVAC operation and exhaust failure resulting in loss of negative pressure. A suspension of optical brightener powder and water was nebulized to produce fluorescent particles simulating droplet nuclei (0.5-5 μm). Airborne particle number concentrations were monitored by Instantaneous Biological Analyzers and Collectors (FLIR Systems). During normal HVAC operation, fluorescent tracer particles were contained in the isolation room (average concentration = 1 × 104 ± 3 × 103 /Lair ). Under exhaust failure, the automated HVAC system maximizes airflow into areas adjacent to isolation rooms to attempt to maintain negative pressure differential. However, 6% of the fluorescent particles were transported through cracks around doors/door handles out of the isolation room via airflow alone and not by movement of personnel or doors. Overall, this study provides a systematic method for evaluating capabilities to contain aerosolized particles during various HVAC scenarios. Recommendations are provided to improve situation-specific BCU safety.

特别声明

1、本页面内容包含部分的内容是基于公开信息的合理引用;引用内容仅为补充信息,不代表本站立场。

2、若认为本页面引用内容涉及侵权,请及时与本站联系,我们将第一时间处理。

3、其他媒体/个人如需使用本页面原创内容,需注明“来源:[生知库]”并获得授权;使用引用内容的,需自行联系原作者获得许可。

4、投稿及合作请联系:info@biocloudy.com。