Diagnosis of Reverse-Connection Defects in High-Voltage Cable Cross-Bonded Grounding System Based on ARO-SVM.

阅读:5
作者:Ai Yuhao, Song Bin, Wu Shaocheng, Li Yongwen, Lu Li, Wang Linong
High-voltage (HV) cables are increasingly used in urban power grids, and their safe operation is critical to grid stability. Previous studies have analyzed various defects, including the open circuit in the sheath loop, the flooding in the cross-bonded link box, and the sheath grounding fault. However, there is a paucity of research on the defect of the reverse direction between the inner core and the outer shield of the coaxial cable. Firstly, this paper performed a theoretical analysis of the sheath current in the reversed-connection state and established a simulation model for verification. The outcomes of the simulation demonstrate that there are significant variations in the amplitudes of the sheath current under different reversed-connection conditions. Consequently, a feature vector was devised based on the amplitude of the sheath current. The support vector machine (SVM) was then applied to diagnose the reversed-connection defects in the HV cable cross-bonded grounding system. The artificial rabbits optimization (ARO) algorithm was adopted to optimize the SVM model, attaining an impressively high diagnostic accuracy rate of 99.35%. The effectiveness and feasibility of the proposed algorithm are confirmed through the analysis and validation of the practical example.