Quartz Crystal Microbalance with Dissipation: A New Approach of Examining Corrosion of New Copper Surfaces in Drinking Water

耗散型石英晶体微天平:一种检测饮用水中新型铜表面腐蚀的新方法

阅读:1

Abstract

Corrosion of copper material in drinking water systems causes public health concerns and plumbing failures. This study investigated the early corrosion of new copper surfaces in situ using a novel technique: quartz crystal microbalance with dissipation (QCMD). The QCMD results showed that increasing the water pH from 6.5 to 9.0 and the addition of 6 mg/L orthophosphate at pH 6.5 and 9.0 slowed down the copper surface mass changes as indicated by the reduced changes in frequency (Δf5) at 51-89% and total copper release at 29-72%. The water pH 9.0 without orthophosphate was the most likely to induce localized corrosion relative to other conditions at pH 6.5 and pH 9.0 with orthophosphate. Based on the changes in dissipation values (ΔD5) from QCMD and the morphology, microstructure, and composition of the deposited copper corrosion byproducts, digital microscopy, field-emission scanning electron microscopy with energy dispersive spectroscopy, and X-ray photoelectron spectrometry analyses confirmed that the pH and orthophosphate inhibited copper corrosion with different mechanisms. QCMD provided sensitive, rapid, and continuous responses to mass and surface changes and can be useful for evaluating early water corrosivity to new copper.

特别声明

1、本页面内容包含部分的内容是基于公开信息的合理引用;引用内容仅为补充信息,不代表本站立场。

2、若认为本页面引用内容涉及侵权,请及时与本站联系,我们将第一时间处理。

3、其他媒体/个人如需使用本页面原创内容,需注明“来源:[生知库]”并获得授权;使用引用内容的,需自行联系原作者获得许可。

4、投稿及合作请联系:info@biocloudy.com。