Transformer fault identification based on GWO-optimized Dual-channel M-A method

基于GWO优化双通道MA方法的变压器故障识别

阅读:1

Abstract

In order to improve the accuracy of the transformer fault identification using nature-inspired algorithms, an identification method based on the GWO (Grey Wolf Optimizer)-optimized Dual-channel MLP (Multilayer Perceptron)-Attention is proposed. First, a Dual-channel model is constructed by combining the AM (Attention Mechanism) and MLP. Subsequently, the GWO algorithm is used to optimize the number and the nodes of the hidden layer in the Dual-channel MLP-Attention model. Typical transformer faults are simulated using DDRTS (Digital Dynamic Real-Time Simulator) system. Experiments showed that the GWO- optimized method has an accuracy rate of 95.3%-96.7% in identifying the transformer faults. Compared with BP, SVM, MLP, and single-channel M-A models, the proposed method improved the accuracy by14.1%, 9.6%, 9.3%, and 3.3% respectively. This result indicates the rationality and effectiveness of the proposed method in transformer fault identification.

特别声明

1、本页面内容包含部分的内容是基于公开信息的合理引用;引用内容仅为补充信息,不代表本站立场。

2、若认为本页面引用内容涉及侵权,请及时与本站联系,我们将第一时间处理。

3、其他媒体/个人如需使用本页面原创内容,需注明“来源:[生知库]”并获得授权;使用引用内容的,需自行联系原作者获得许可。

4、投稿及合作请联系:info@biocloudy.com。