Exploring Regional Fine Particulate Matter (PM(2.5)) Exposure Reduction Pathways Using an Optimal Power Flow Model: The Case of the Illinois Power Grid

利用最优潮流模型探索区域细颗粒物(PM2.5)暴露减少路径:以伊利诺伊州电网为例

阅读:1

Abstract

This work develops an exposure-based optimal power flow model (OPF) that accounts for fine particulate matter (PM(2.5)) exposure from electricity generation unit (EGU) emissions. Advancing health-based dispatch models to an OPF with transmission constraints and reactive power flow is an essential development given its utility for short- and long-term planning by system operators. The model enables the assessment of the exposure mitigation potential and the feasibility of intervention strategies while still prioritizing system costs and network stability. A representation of the Illinois power grid is developed to demonstrate how the model can inform decision making. Three scenarios minimizing dispatch costs and/or exposure damages are simulated. Other interventions assessed include adopting best-available EGU emission control technologies, having higher renewable generation, and relocating high-polluting EGUs. Neglecting transmission constraints fails to account for 4% of exposure damages ($60 M/y) and dispatch costs ($240 M/y). Accounting for exposure in the OPF reduces damages by 70%, a reduction on the order of that achieved by high renewable integration. About 80% of all exposure is attributed to EGUs fulfilling only 25% of electricity demand. Siting these EGUs in low-exposure zones avoids 43% of all exposure. Operation and cost advantages inherent to each strategy beyond exposure reduction suggest their collective adoption for maximum benefits.

特别声明

1、本页面内容包含部分的内容是基于公开信息的合理引用;引用内容仅为补充信息,不代表本站立场。

2、若认为本页面引用内容涉及侵权,请及时与本站联系,我们将第一时间处理。

3、其他媒体/个人如需使用本页面原创内容,需注明“来源:[生知库]”并获得授权;使用引用内容的,需自行联系原作者获得许可。

4、投稿及合作请联系:info@biocloudy.com。