Abstract
Icing on transmission lines in cold regions can cause asymmetry in the conductor cross-section. This asymmetry can lead to low-frequency, large-amplitude oscillations, posing a serious threat to the stability and safety of power transmission systems. In this study, the aerodynamic characteristics of crescent-shaped and sector-shaped iced eight-bundled conductors were systematically investigated over an angle of attack range from 0° to 180°. A combined approach involving wind tunnel tests and high-precision computational fluid dynamics (CFD) simulations was adopted. In the wind tunnel tests, static aerodynamic coefficients and dynamic time series data were obtained using a high-precision aerodynamic balance and a turbulence grid. In the CFD simulations, transient flow structures and vortex shedding mechanisms were analyzed based on the Reynolds-averaged Navier-Stokes (RANS) equations with the SST k-ω turbulence model. A comprehensive comparison between the two ice accretion geometries was conducted. The results revealed distinct aerodynamic instability mechanisms and frequency-domain characteristics. The analysis was supported by Fourier's fourth-order harmonic decomposition and energy spectrum analysis. It was found that crescent-shaped ice, due to its streamlined leading edge, induced a dominant single vortex shedding. In this case, the first-order harmonic accounted for 67.7% of the total energy. In contrast, the prismatic shape of sector-shaped ice caused migration of the separation point and introduced broadband energy input. Stability thresholds were determined using the Den Hartog criterion. Sector-shaped iced conductors exhibited significant negative aerodynamic damping under ten distinct operating conditions. Compared to the crescent-shaped case, the instability risk range increased by 60%. The strong agreement between simulation and experimental results validated the reliability of the numerical approach. This study establishes a multiscale analytical framework for understanding galloping mechanisms of iced conductors. It also identifies early warning indicators in the frequency domain and provides essential guidance for the design of more effective anti-galloping control strategies in resilient power transmission systems.